hw:zelio
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| hw:zelio [2010/05/10 16:33] – Added SR3NET01BD link pkubanek | hw:zelio [2020/09/28 21:30] (current) – pkubanek | ||
|---|---|---|---|
| Line 2: | Line 2: | ||
| ====== Zelio roof control ====== | ====== Zelio roof control ====== | ||
| - | This is a roof module | + | This is a roof module |
| - | Schneider Zelio logic editor. The editor | + | Schneider Zelio logic editor, which runs under Wine in Linux. |
| details if you cannot get it running. | details if you cannot get it running. | ||
| - | The programme | + | The program |
| - | closing, four end -of-path sensors and two motors. If your needs are different, | + | please either help yourself or contact Petr Kubanek with questions. |
| - | please either help yourself or contact Petr Kubanek with questions. PLC has attached | + | |
| - | There is a picture of front panel. In our experiences, nothing beats hardware switches when it comes to reliably | + | There is a picture of front panel. In our experience, nothing beats hardware switches when it comes to reliably |
| - | {{: | + | {{: |
| - | The programme | + | The program |
| - | * auto/manual switch | + | * auto/ |
| * close/open switch for manual operation | * close/open switch for manual operation | ||
| - | * four switches | + | * four switch inputs |
| * control for four motor relays - two per motor (open and close direction) | * control for four motor relays - two per motor (open and close direction) | ||
| - | * attached ethernet module with dead-man | + | * attached ethernet module with dead-man's handle |
| - | * rain button | + | * rain input (when 1, it is not raining) |
| * configurable timeout for roof closing/ | * configurable timeout for roof closing/ | ||
| * configurable timeout for time between roof closing/ | * configurable timeout for time between roof closing/ | ||
| - | * independent operation of both roof halfs, governed by power sensing input (I9) | + | * independent operation of both halves of the roof, governed by power sensing input (I9) |
| - | * any timeout (openign | + | * any timeout (opening |
| ===== Inputs ======= | ===== Inputs ======= | ||
| - | * **I1** Manual/Auto operation. If it is 1, roof is in auto operation. In auto mode, roof will not follow | + | * **I1** Manual/Auto operation. If on, the roof is operating automatically, and will ignore inputs from **I2**, accepting |
| | | ||
| - | * **I2** Open/Close switch. Only active | + | * **I2** Open/Close switch. |
| - | * **I3, I4, I5, I6** Inputs for end-of path switches. Please see provided description for details. | + | * **I3, I4, I5, I6** Inputs for end-of path switches. Please see the provided description for details. |
| - | * **I7** | + | * **I7** |
| - | * **I8** Emergency stop. If engaged, | + | * **I8** Emergency stop. If engaged, |
| - | * **I9** Power sensing. If 1, there is power in the grid. | + | * **I9** Power sensing. If on, grid electricity is available. |
| ===== Outputs ======= | ===== Outputs ======= | ||
| - | * **Q1, | + | * **Q1, |
| - | * **Q8** is engaged in emergency situation - e.g. when timeout | + | * **Q8** is engaged in emergency situation - e.g. when a timeout |
| - | * **Q9** is extra switch, used for all-sky | + | * **Q9** is extra, |
| ===== Ethernet inputs ====== | ===== Ethernet inputs ====== | ||
| - | * **J1XT1** 7 low bits are used for timeout control. So 127 seconds is maximal timout for roof control. The most significant bit - bit 16 - is used for weather override - if set to 1, roof will operate from computer even if it is raining. Bit 15 (4000) is used for control of Q9 switch. | + | * **J1XT1** 7 low bits are used for timeout control. So 127 seconds is maximal timout for roof control. The most significant bit (16) is used for weather override - if set to 1, roof will operate from computer even if it is raining. Bit 15 (4000) is used for control of Q9 switch. |
| - | * **J2XT1** Dead man button control. Ethernet | + | * **J2XT1** Dead man's handle. The ethernet |
| ===== Ethernet outputs ====== | ===== Ethernet outputs ====== | ||
| Line 62: | Line 61: | ||
| * **Q2XT1** State of left half of the roof. | * **Q2XT1** State of left half of the roof. | ||
| - | * **Q3XT1** Number of seconds remaining | + | * **Q3XT1** Number of seconds remaining |
| * **Q4XT1** State of various emergency and other signals | * **Q4XT1** State of various emergency and other signals | ||
| Line 68: | Line 67: | ||
| ===== Roof states reported in ethernet outputs ====== | ===== Roof states reported in ethernet outputs ====== | ||
| - | Each output is threated | + | Each output is treated |
| - 0001 not used | - 0001 not used | ||
| Line 86: | Line 85: | ||
| The device state (Q4XT1): | The device state (Q4XT1): | ||
| - | - 0001 state of manual/auto switch | + | - 0001 state of manual/auto switch |
| - | - 0002 state of close/open switch. | + | - 0002 state of close/open switch |
| - 0004 timeout occured - emergency declared | - 0004 timeout occured - emergency declared | ||
| - | - 0008 power sensing (I9) - not pressent | + | - 0008 power sensing (I9) - not present |
| - 0010 rain declared | - 0010 rain declared | ||
| - 0020 compressor running - only on model with compressor | - 0020 compressor running - only on model with compressor | ||
| Line 99: | Line 98: | ||
| - 0800 compressor (B2) model * | - 0800 compressor (B2) model * | ||
| - 1000 weather state - 1 if weather is favorable for observing | - 1000 weather state - 1 if weather is favorable for observing | ||
| - | - 2000 ignore rain during opening - know problem | + | - 2000 ignore rain during opening - a known problem |
| - 4000 emergency button pushed | - 4000 emergency button pushed | ||
| - 8000 state of deadman signal | - 8000 state of deadman signal | ||
hw/zelio.1273509186.txt.gz · Last modified: 2010/05/09 22:00 (external edit)